Modbus Programming Manual ADDRESS LIST
Version 2 43
Copyright © 2012 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Wait until time of the day “B” in seconds since
midnight.
Number of times to
repeat 1 to 9999
Loop to the specified segment number “B” from this
point. Repeat this “A” times. Only segments below the
current segment can be entered. Two loops must not
cross each other.
On completion of this profile jump run profile “B”
Turn off all control outputs.
1 = Maintain profile
setpoint
Stay at the final setpoint of the profile
2 = Control off with
events
Turn off the outputs but maintain the events.
Number of times to
repeat sequence
Repeat the profile sequence number “B” times, then
turn off the control outputs
1 = Maintain profile
setpoint
Repeat the profile sequence number “B” times, then
hold the last profile setpoint.
2 = Control off with
events
Turn off the outputs but maintain the events.
2.9.5.6. Deleting Profiles (Command Code DP and DA)
An individual profile can be deleted, or all profiles can be cleared with a single message.
Deleting a profile removes the header of the specified profile and any segments associated with it.
Delete all profiles wipes all profiles and segments from the instrument.
Delete Profiles - Request (to instrument)
The ID address of the instrument.
Requires the multi read/write function
Read Start Address High Byte
Read Start Address Low Byte
Read Quantity Of Registers High
Read Quantity Of Registers Low
Write Quantity Of Registers High
Write Quantity Of Registers Low
Delete A Profile (DP) = 02dec / 0x02hex
Delete All Profiles (DA) = 01dec / 0x01hex
Delete A Profile (DP) = 04dec / 0x04hex
Delete All Profiles (DA) = 02dec / 0x02hex
Delete A Profile (DP) = 17488dec /
0x4450hex
Delete All Profiles (DA) = 17473dec /
0x4441hex
Note: The profile number is not included
in the message when deleting all profiles.
The instrument replies to this message with an Edit Response Message Section 2.9.5.9.