Despatch LAD Series WITH PROTOCOL PLUS Manual do Utilizador Página 51

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 50
43
Quick Reference and Default Values
Program Page
Menu Item
Display
Default
Range
Setting
Ramp Time Seg 1
Pro-1 Seg-1 Ramp Time
00:00
00m00s to
99h59s
Event 1 Set Value
Pro-1 Seg-1 Ramp Event 1
Off
Off, On
Event 2 Set Value
Pro-1 Seg-1 Ramp Event 2
Off
Off, On
Event 3 Set Value
Pro-1 Seg-1 Ramp Event 3
Off
Off, On
Event 4 Set Value
Pro-1 Seg-1 Ramp Event 4
Off
Off, On
Soak Temp Seg 1
Pro-1 Seg 1 Soak Temp
68°F
SPLowerLim to
SPUpperLim *
Soak Time Seg 1
Pro-1 Seg 1 Soak Time
00:00
00m00s to
99h59s
Event 1 Set Value
Pro-1 Seg-1 Soak Event 1
Off
Off, On
Event 2 Set Value
Pro-1 Seg-1 Soak Event 2
Off
Off, On
Event 3 Set Value
Pro-1 Seg-1 Soak Event 3
Off
Off, On
Event 4 Set Value
Pro-1 Seg-1 Soak Event 4
Off
Off, On
(repeat for segments 2-8)
High Limit Setpoint
Pro-1 Hi-Lim SP
Max
HiLimSP
MinHiLimSP to
MaxHiLimSP *,
Band **
Loop From
Pro-1 Loop From XX
No
No, Seg-1 to
Seg-8
Loop To
Pro-1 Loop To XX
No
No, Seg-1 to
Seg-8
Loop Count
Pro-1 Loop Number
0
0 to 99
Profile Link
Pro-1 Link To XX
Stop
Standby***,
Stop, Hold,
Pro-1 to Pro-8
Guaranteed Soak
Pro-1 Guar Band
Off
Off, 1 to 778°C
(1400°F)
(repeat for profiles 2-8)
* See Enable Page
** Band value is set on Control Page
*** If Standby
1. Cycle Complete LED indication goes ON.
2. Controller beeps if End Of Cycle beep is enabled.
3. Heater/control output keeps controlling oven temperature at last Soak setpoint.
4. All events programmed (if relay cards installed and programmed as an event) for
the last Soak Segment stays active.