Despatch/Watlow 1500 Control Instruction Manual Page 13
LPB Series Guarded Access Chart
Make a copy of this chart to document the Series 1500
Guarded Access for each program you use.
Program #_____ System _______ Programmer ________ Date__________
GA Code Ch Pmpt Parameter Typical HASP Settings Your Settings
0000 C1 UP Ch-1 Upper Process Alarm 170
C1 LP Ch-1 Lower Process Alarm 0
C1 Ud Ch-1 Upper Deviation Alarm 538
C1 Ld Ch-1 Lower Deviation Alarm -538
C2 UP Ch-2 Upper Process Alarm 101
C2 LP Ch-2 Lower Process Alarm -001
C2 Ud Ch-2 Upper Deviation Alarm 101
C2 Ld Ch-2 Lower Deviation Alarm -101
0005 RC Recycle 0000
C1 Pb Ch-1 Prop. Band 0003
C1 RS Ch-1 Reset 0005
C1 RT Ch-1 Rate 0001
C1 Rb Ch-1 Rate Band 0001
C1 CT Ch-1 Cycle Time 0001
C1 db Ch-1 Dead Band 0000
C1 CA Ch-1 Calibration Adjust. 0000
C2 Pb Ch-2 Prop. Band 0005
C2 RS Ch-2 Reset 0002
C2 RT Ch-2 Rate 0005
C2 Rb Ch-2 Rate Band 0001
C2 CT Ch-2 Cycle Time 0001
C2 db Ch-2 Dead Band 0000
C2 CA Ch-2 Calibration Adjust. 0000
0006 U1 Ch-1 Upper Set Point Limit 166
L1 Ch-1 Lower Set Point Limit 0
U2 Ch-2 Upper Set Point Limit 100
L2 Ch-2 Lower Set Point Limit 000
RC Recycle: ON = 1, OFF = 0 0
TT T-RH = 0000, T-T = 0001 0
Ad Address number RS-422 0